How to change the HTTP user name and password on the FactoryCast 140NOE77111 module.

Title
FactoryCast 140NOE77111  Change User name and password
 
Issue
How to change the HTTP user name and password on the FactoryCast 140NOE77111 module.
 
Product Line
Quantum
 
Resolution
 Below is a step by step procedure


Launch the FactoryCast Configurator tool



Open the File tab and select New Configuration



Under the Password tab change User Name and Password
Hit OK



Open the Transfer tab and select Security File



Insert the IP address of the FactoryCast NOE77111
Hit OK



When transfer process is complete recycle power to the NOE771 module by re-seating it



Launch IE and try the new User Name and Password