Is it possible to send E-mails from Web Gate?

Goals and Symptoms

In Vijeo-Designer, it is possible to send e-mails from HMI Runtime. This e-mail feature for Vijeo Designer Runtime however does not function on a Web Gate Client.

Causes and Fixes


When the Email feature is configured for Vijeo Designer Runtime, the user must realize that this feature is not supported for Web Gate. Any switches or actions configured to send an email on the HMI side will not do anything in Web Gate.

The workaround is to create a global action that is triggered by a bit that is shared with Web Gate. When the user presses the switch to trigger the bit, the corresponding action on the HMI will send the email as expected.
 

 