ATV71/ATV61 getting CLI during normal operation


Issue:
ATV71/ATV61 getting CLI during normal operation
 
Product Line:
 ATV61/71

Environment:
CL1
 
Cause:
Drive: ATV71HD55N4, appl-soft 1.2IE12, comm-card VW3A3307. Motor: 55kW, 400V, 97A. In normal run the drive displays CLI, motor current displayed =37A (checked with external measurement). Current limitation 1 and 2 are set to 174A. The drive does not trip under theese conditions, but trips for overload when overloaded. Only status seems to be incorrectly displayed.

Resolution:
The indication CLI is for the display and this value is not filtered compare to the value of the current LCR which it is filtered. On certain applications if the current is unstable then the drive is going to display CLI (peaks) while the current displayed LCR is lower (average). The instabilities can be due to a rigid speed loop. Decrease SPG and\or increase SIT.

The display of CLI can come from :
- the drive reach the current limitation (CLI) set in 1.3 setting menu,
- the drive does not follow the acceleration ramp (increase to see if this is it),
- the drive is in voltage limitation, this can come from the voltage drop in DC choke, or the main voltage which is not enough high,

To decrease the switching frequency can decrease voltage drop in DC choke and make the drive not be in CLI. You can also try to use an other law.