Why does my Altivar drive have no display?

Published date: 23 September 2019

Issue:
MyAltivar drive does not have a display?

Product Line:
All Altivar drives
 
Environment:
Display doesn't light up
 
Cause:
n/a
 
Resolution:
Measure the input voltages (phase to phase) at L1, L2 and L3
Measure the DC bus at PA+ and PC-. DC voltage measurement should be ~1.41 times your line voltage. 
Measure the +24v and +10v supplies. Measure to COM, not ground.
If the DC bus is ok, but the 24Vdc or 10Vdc is missing, then could be a problem with the Main Control board and/or the Power Board of the drive.
 
 
 