What is the wait time to reset SnbF on an ATS22?

Issue:
When the ATS22 trips on SnbF, the fault does not reset immediately. 

Product Line:
ATS22

Environment:
All models and frame sizes

Cause:
The number of starts set by Snb and SLG has been exceeded.

Resolution:
SNBF cannot be cleared by powering down the softstart.
One way to clear the fault is to wait with power still applied to the softstart.
The wait time depends on the frame size.  The control power must be on to run the timer.
Frame size A is 5 minutes.
Frame size B, C, D and E is 15 minutes.