Technical FAQs

Ask a Question

How to program the ATV61 or ATV71 drive for reference switching between 2 channels?

Issue:  
How to program the ATV61 or ATV71 drive for reference switching between 2 channels?

Product Line: 
ATV61, ATV71
 
Environment
All

Cause:
Setup instructions request

Resolution:
CtL ( Command menu )
Set ref 1 ch (Fr1) to the desired reference for the (hand) position
FuN menu ( Application Function ) 
Reference Switching
Set Ref 1B sw (rCb) to  the desired logic input ( LIx)
Set Ref 1B ch (Fr1b) to the desired reference for the (auto) position
Operation: Hand position LIx = not active (Fr1)  and LIx = active (Fr1b)

Example:  
Wants to run from a potentiometer wired to AI1 in Hand or Local mode and wants to run from a 4-20mA signal on AI2 when in Auto or Remote mode.  
Has his Hand/Auto selector switch wired so in Hand LI3 is off and in Auto LI3 is on.
Goto Menu 1.6 [Command] and program Ref 1 Channel to AI1.
Goto Menu 1.7 [Application Function] - Reference Switch submenu and program Ref 1B switching to LI3 and Ref 1B Channel to AI2.
Was this helpful?
What can we do to improve the information ?