What circuit breaker types will an QMBJW, QMB branch circuit breaker unit accept?

Issue:
What circuit breakers can be used in the QMBJW?

Product Line:
QMB panelboard, switchboard with QMB distribution.

Environment:
Products sold and used in the United States.

Cause:
Not all of the PowerPact J frame breakers should be used in the QMBJW.  The JJA and JLL types are not listed for use in the QMBJW.

Resolution:
The QMBJW will accept the 150a to 225a JDL and JGL type circuit breakers. as stated in the QMBJW labels.