Why will the analog output not change when the AO1 assignment is set to Torque 4Q?

Issue:
 The Analog output is fixed at 50% and not changing as the torque in the motor changes (Fixed at 10mA when the Analog output is set to 0-20mA, fixed at 12 mA when the Analog output is set to 4-20mA)
 
Product Line:
 Altivar 71
 
Environment:
 All part numbers all versions
 
Cause:
 The motor control type is set to either V/F 2pts or V/F 5pts
 
Resolution:
The Motor control type must be set to something other than V/F 2pts or V/F 5pts for this function to work.   Once the Motor Control type has been changed the analog output should begin to respond to changes in the motor torque.