Is there an Ethernet TCP/IP option on the ATS22 Soft Starter?

Issue:
Is there an Ethernet TCP/IP option on the ATS22 Soft Starter?

Product Line:
Altistart ATS22

Environment:
All

Cause:
Ethernet option on the ATS22 Soft Starter

Resolution:
The Soft Starter has a built-in Modbus port. A Modbus-to-Ethernet Gateway (EGX100SD) can be used to interface between Modbus and Ethernet communication.