Technical FAQs

Ask a Question

QO-GFI: Needing assistance with troubleshooting his application.

Issue:
QO-GFI: needing assistance with troubleshooting his application.

Product Line:
Circuit Breakers

Environment:
Applies to QO-GFI or HOM-GFI breakers

Resolution:

Test the breaker:
1.  Remove load wires and turn on the breaker
2.  The breaker should trip with the yellow test button.   If it does both of these, then the breaker is functioning properly.

Installation:
1.  Pigtail wire goes to the neutral bar.   
2.  Black and white load wires to the breaker.

Wiring:
1.  Neutral and ground isolated in a sub panel
2.  Check for grounded neutrals, by checking continuity between ground and white load neutral wire.  (remove the load white wire from the breaker while doing this test).  Should have no continuity.  If continuity, then check wiring for neutral and ground wires touching.
Was this helpful?
What can we do to improve the information ?