Is there a replacement for the DJM32400E20 used in the 400A EZML or EZMK Branch Metering Devices?

Issue:
The DJM32400E20 tenant circuit breaker in a 400A EZML or EZMK, Series M02, needs to be replaced.

Product Line:
Metering Equipment.

Environment:
EZ Metering Devices.

Resolution:
The DJM32400E20 can be replaced with the LJL36400U31X. A mounting kit, S36967, is also required. The lugs on the OFF end of the LJL36400U31X must be removed to allow for connection to the busbars. When the EZML branch is a single phase device, the B phase (center) lug should also be removed from the ON end of the breaker.
 