What breakers can be used in a QO2L30S load center?

ISSUE:
What breakers will fit in a QO2L30S?

PRODUCT LINE:
Load Centers

ENVIRONMENT:
QO Load Centers

RESOLUTION:
The QO2L30S will accept (1) double pole or (2) single pole QO breakers. It will not accept type QO-EPD, QO-GFI, QO-AFI, QOB, QOT tandem or QO tandem circuit breakers. This is a 2 space/2 circuit panel, accepting full size QO branch circuit breakers only. The 30 ampere panel rating should not be exceeded, or 25 ampere when aluminum feeder wire is used.