Can a shunt trip be added to QO/B or QOU breakers?

Issue:
Are QO/B and QOU breakers available with a Shunt Trip?

Product Line:
Circuit Breakers

Environment:
Applies to QO, QOB, QOU circuit breakers
Does NOT apply QO or QOB breakers with suffix GFI, EPD, EPE, AFI, CAFI, DF
Does NOT apply to QOB-VH (2P 150A and 3P 110 to 150A) or QO/B 2P 150A-200A
Does NOT apply to QO tandems or QOT tandems
Does NOT apply to QO or QOU molded case switches

Resolution:
Shunt trip This can be factory installed only on QO/B, QO/B-SWN, and QOU by adding suffix:
  • 1042 for 12 or 24 Vac or Vdc
  • 1021 for 120, 208 or 240 Vac
The shunt trip terminals accept (2) 14-12 AWG CU wires. The HOT or Neutral wires can be connected to either terminal. The shunt trip adds an additional pole space to the breaker.