How can the ATV212 or ATV21 be set up for start/stop on terminal and ramp to 60 Hz?

Issue:
How can the ATV212 or ATV21 be set up for start/stop on terminal and ramp to 60 Hz?

Product Line:
ATV21, ATV212

Environment:
All models and serial numbers.

Cause:
None

Resolution:
Begin by wiring the remote start switch or relay for two wire control between terminals P24 and F. 

Program the nameplate motor parameters into the following parameters: 
CODE - DESCRIPTION
thr - Motor thermal prot.
uLu - Motor rated voltage
F415 - Motor rated current
F417 - Motor rated speed

Make the following parameter settings:
CODE - DESCRIPTION SETTING
LL - Low limit frequency as desired
UL - Upper limit freq 60
Dec - Deceleration ramp time as desired
ACC - Acceleration ramp time as desired
CMOD - Command mode selection 0