Will the ATV212 and ATV312 drives have output phase loss protection?

Issue:
Looking for protection from the loss of an output phase. 

Product Line:
Altivar 212, Altivar 312

Environment:
All models, all serial numbers. 

Cause:
Phase protection

Resolution:
Both the ATV312 and ATV212 have output phase loss protection. 

Output phase protection can be disabled on both of these drives.
For the ATV312 go to FLT > OPL and change from YES to NO to disable phase protection.
For the ATV212, hit Mode until you see AUF, then scroll down to F - - - and hit Enter.  Scroll down to F605 and change to 0 to disable.