Technical FAQs

Ask a Question

How can ATS01N2...LU, QN, RT be started without control wires?

Issue:
How can ATS01N2...LU, QN, RT be started without control wires?

Product Line:
Altistart 01 Soft Starters with "LU", "QN", or "RT" at the end of the part number

Environment:
All

Cause:
Need to start the Soft Starter with power up

Resolution:
Add a jumper between terminals LI+ and LI2.  This provides a continuous RUN command.  When power is supplied to the ATS01, it will immediately begin to start the motor.  Removing power will result in a freewheel stop.

 
Was this helpful?
What can we do to improve the information ?