Can a 20 amp or 30 amp EH or EHB breaker be installed opposite an EHB34100 ?

Issue:
Can a 20 amp or 30 amp EH , or EHB Bolt on breaker, be installed opposite an EHB34100  ?

Product Line:
NEHB Panlboard

Environment:
Installation

Cause:
Clarification

Resolution:
No . You can not place any breaker across from 70-100A  EHB breakers.  They have a rejection feature which prevents it and that is due to heat issues.
The NEHB panel and Eh/EHB breakers are obsolete and no longer supplied by Square D /Schnedier Electric. The NF Panelboard with ED/EDB breakers, are currently offered 



 