What is the fault code PRA on ATV61 or ATV71 drives?

Issue:
What is the fault code PRA on ATV61 or ATV71 drives? 

Product Line:
Altivar ATV61 ATV71

Environment:
All

Cause:
Drive status is showing PRA on the HMI display.

Resolution:
PRA is not a fault, but it is a drive state, meaning that the power removal function is active. The drive is not detecting 24Vdc on the PWR terminal.
Measure for 24Vdc between +24 - COM to verify the internal power supply.
Confirm that the factory installed jumper between +24 and PWR is solidly connected.  The jumper is removed if a safety circuit is installed.  Verify continuity of the safety circuit.

When the voltage on PWR is re-established, the drive status will return to RDY if there is not an active run command, or NST if a run command is active.  To clear NST, remove the run command.
 