Is a 50A main breaker available in a NQ panelboard?

Issue:
Can a 50A main breaker be used on an NQ panelboard?

Product Line:
Panelboards

Environment:
NQ

Cause:
Product offering

Resolution:
No, per NEC article 230.79, the minimum main breaker needs to be at least 60A.