What is the max distance for a 225 amp Powerbus busway run , is voltage drop an issue?

Issue:
Is there a voltage drop for a 225 amp Powerbus busway run , is voltage drop an issue?

Product Line:
Busway

Environment:
Amperage selection of Busway with voltage drop concern

Cause:
With layout and distances there is a concern about voltage and amperage drop usually associated with wire and conduit

Resolution:
There is no maximum distance restrictions using the 225 amp Powerbus busway, but it DOES have a 2.5Volt drop / per every 100` . This is based on a100% power factor (Pf).








 