Can the Altivar 312 drive be set up to start with a run command active or to restart without requiring the run command to be cycled in the event of a power outage?

Issue:
Can the Altivar 312 drive be set up to start with a run command active or to restart without requiring the run command to be cycled in the event of a power outage?
 
Product Line:
ATV312
 
Environment:
Power outage
 
Cause:
n/a
 
Resolution:
Yes it can. If the drive is set for 2 wire control  In the IO menu, set tCC-2C and tCt-LEL (LI1- Run Forward).   Go to FLT menu: Set Atr to yes. The same logic will apply to the run reverse command ( LI2).
 