Can PowerPact breakers be used on a Corner grounded (grounded B phase) delta system?

Issue:
Can PowerPact breakers be used on a Corner grounded (grounded B phase) delta system?

Product Line:
PowerPact Molded Case Circuit Breakers

Environment:
This applies to 2P and 3P PowerPact Breakers.

Cause:
How are breakers applied to these systems?

Resolution:
Yes, the PowerPact breakers can be used on both 3 phase 240 and 480v corner grounded delta systems.
For 240Vac corner grounded systems, only 2P breakers are listed.
For 480Vac corner grounded systems, only 3P breakers are listed.
See the attached file for additional information: