What is the maximum wire size for the lugs for H frame breakers?

Issue:
What is the wire size for the lugs for H frame breakers?

Product Line:
Powerpact Breaker 

Environment:
Powerpact H Frame Breakers

Resolution:

The lugs for Powerpact H frame breakers can accommodate a maximum of 3/0 wire. See below.

AL150HD  (1) #14 - 3/0 AWG Al or Cu
CU150HD (1) #14 - 2/0 AWG Cu