How do power terminal protection shrouds such as an LA9F703 fit on the F-Line contactors? Will they work with the DZ2 type lugs?

Product Line:
 
Tesys F line Contactors and Accessories
 
Resolution:
 First, the LA9 shrouds do not work with the DZ type lugs. They work with compression type lugs such as large ring tongue terminals. When the compression lugs are bolted to the contactor terminals, the threaded portion of the bolt facing the front of the contactor provides a threaded area for the shroud to attach to. The plastic shroud is secured by the bolt threads, and covers and insulates the compression terminal.


 