Is a D224NRB safety switch suitable for use as service equipment?

Issue:
Service Entrance application for D224NRB.
 
Product Line:
Safety Switch
 
Environment:
General Duty Safety Switch
 
Resolution:
Yes, this switch is UL Listed and labeled as ``Suitable For Use As Service Equipment``. For a service equipment application, the neutral should be bonded to the enclosure with the green hued neutral bonding screw that was supplied with the safety switch.