Does the FFTK report generator software work with the Windows 7 or Windows 10 operating system?

Inquiry:
Can the FFTK report generator software for testing Micrologic trip units FFTKRPT-V1-0 (FFTKRPTV10) be used with Windows 7, Windows 8, or the Vista operating systems?

Product Line:
Micrologic trip units for Powerpact M, P, R frame and Masterpact NW and NT

Cause:
Users are upgrading the now obsolete XP operating systems and going to Windows 7 and Windows 10

Resolution:
The Report Generator software will not work on Windows 10.  
It will work on Windows 7, 8, and Vista but not if you use the default directory provided with the software.  Please use the following work-around:
In order for the FFTK report generator to function properly, you need to have it installed it in a write-accessible folder on your system. Most “new” versions of Windows (Vista, 7, 8) have special permission control on the [C:\Program Files (x86)] and [C:\”Program Files”] folders. On these newer systems we recommend installing the FFTK report generator to somewhere where you have write permissions such as…
For all users of the system: [C:\Users\Public\”Public Documents”\”FFTK Report Generator”].
For a single user: [C:\Users\ \”My Documents”\”FFTK Report Generator”], where is the desired user.

See attachment to download the Report Generator software.
 