When using a NQMB4LA main breaker adapter kit with an LAL36400 breaker, does the customer have to remove lugs to mount the breaker?

Issue:
When using a NQMB4LA main breaker adapter kit with an LAL36400 breaker, does the customer have to remove lugs to mount the breaker?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
Yes. The NQMB4LA has busbar connections, so breaker lugs must be removed to install the main breaker.


 