Can Key Interlocks(KI) be provided on the Circuit Breaker Enclosures used for the Molded Case Breakers (For example the J205S, M800R or P1200AWK circuit breaker enclosures)?

Issue:
Product Design Features

Product Line:
Circuit Breaker Enclosures

Environment:
Key Interlock accessory

Cause:
Application

Resolution:
KI = Key Interlock
MCB = Molded Case Breaker
CBE = Circuit Breaker Enclosure


NOTES:
1) The actual KI accessory itself for the MCB CANNOT be added to the circuit breaker and used inside ANY of the Square D enclosures.
2) The KI that can be provided on the CBE MUST be factory installed ONLY, there are NO Field installed KI options. See below for the enclosures.
3) Key Interlocks CANNOT be added to the NEMA 1, 3R, 7 or 9 enclosures


The Factory ONLY option that can be added to certain CBE's are shown below.
For the Legacy F-Frame enclosures, the FA100DS and FA100AWK are the ONLY two enclosures the KI can be factory added.
For the Legacy L-Frame enclosures, the LA400DS and LA400AWK are the ONLY two enclosures the KI can be factory added.
For the Powerpact J-Frame enclosures, the J250DS, J250SS and J250AWK are the ONLY three enclosures the KI can be factory added.
For the Powerpact L-Frame enclosures, the L600AWK and L600AWKMC(this would include the suffix 'VW') are the ONLY two enclosures the KI can be factory added. 
For the Powerpact M-Frame enclosures, the M800DS, M800SS and M800AWK are the ONLY three enclosures the KI can be factory added.
For the Powerpact P-Frame enclosures, the P1200AWK is the ONLY enclosure the KI can be factory added.

Additional Notes:
See Section 3 of the Supplemental and Obsolescence Digest 177 for additional information.
For quoting purposes, the suffix KI can be added to the enclosure catalog number and the KI price adder PER lock must be added to the list price of the enclosure.
For ordering purposes, contact the Lexington PSG(email = lexpsg@schneider-electric.com) and a special catalog number can be provided based on all the different options and/or accessories that might be required for the application.



 