What is the shunt trip burden or VA for Powerpact H, J and L circuit breakers?

What is the  burden or VA for the AC and DC shunt trips for the Powerpact H and Powerpact J breakers?

Product Line:
Powerpact H, J, L

Electrical distribution

Sizing a power supply

All Powerpact H, J, and L - AC shunt trips have a pickup VA consumption of less than 10VA.
All Powerpact H, J, and L - DC shunt trips have a pickup consumption of less that 5 Watts.

NOTE:  To convert to Amps, divide the VA or Watts by the control Voltage.  VA/V = A and Watts/V = A