Is a single pole I-Line circuit breaker available that is rated at 600 Volts?

Issue:
Is a single pole I-Line circuit breaker available that is rated at 600 Volts?

Product Line:
I line panelboards.

Environment:
Products sold in the United States.

Cause:
Product availability.

Resolution:
The single pole, B-frame I-Line type breakers are limited to 347 Volts maximum per pole (600Y/347 V system). If there is a requirement for a single pole, 600 V phase-to-neutral breaker, it is advisable to use a two pole (ie. BDA260201) and only use one pole.