What is the resistance or ohms value for the TeSys DC Coils on an LC1D09 thru LC1D38?

Product Line:

Tesys D line Contactors
 
Resolution:
 

Please see the table below for these values (within approximately + or - 10%)
 
Voltage Code Resistance (Ohms) Inductance DC Coil Voltage
AD  4.41 0.18 5
AL  9.51 0.37 5
BD  101.9 3.9 24
BL  213.7 8.2 24
CD 207.7 8.1 36
CL 494.8 19 36
DD 1527 55 96
DL  3255 122 96
ED 392.7 15 48
EL 843.6 33 48
FD  2085 78 110
FL 4584 163 110
GD  2539 94 125
JD  26 1 12
JL 53.4 2.1 12
KD  1661 62 100
LD 6262 207 200
MD  7472 268 220
ML  17824 604 220
ND 633.3 24 60
PD  3923 143 155
QD 4845 177 174
RD  29692 923 440
SCD  50973 1653 575
SD 819.9 31 72
SL  1953 71 72
TD 14986 526 305
UD  9580 345 250
UL  22158 745 250
VD  18944 659 348
XD  59146 2053 600
ZD 66.4 2.6 20
ZL 147.6 5.5 20

 