Are the enclosures (cans or boxes) ONLY available for the QO and Homeline Load Centers?

Issue:
Design Repair parts

Product Line:
QO and Homeline Load Centers

Environment:
Repair parts

Cause:
Maintenance

Resolution:
No.  Enclosures (cans or boxes) ONLY are NOT available as replacement items for any QO or Homeline Load Centers.  The labeling on the enclosure and interior will not match and this will violate the UL listing and the conformity to the National Electrical Code (NEC).  The box label and interior label must match per NEC 110-3B code for labeling.