What is the difference between the GV2L and GV2ME?

Issue:
GV2L and GV2ME specs

Product Line:
GV Manual Motor Starters and Protectors

Environment:
North American Products
 
Resolution:
The GV2L devices are similar to the GV2M manual starters but provide magnetic protection only. The GV2M devices provide thermal overload protection as well. Neither device is UL489 listed for use as a circuit breaker in the United States.