What type of wire binding screw is used with AL150HD lugs and what size it? What is the size or type of tool that is used to torque them?

Issue:
What size Allen wrench should be used on AL150HD?

Product Line:
Powerpact H-Frame

Environment:
Powerpact H-Frame Lug

Resolution:
An Allen wire binding screw is used and a 3/16`` Allen wrench is needed to torque screws to 50 in lbs for #14-#10 awg wire and 120 in. lbs for #8-3/0 Al/Cu conductors.