Can a Model 5 MCC Bucket be placed in new Model 6 MCC section

Issue:
Can  a Model 5 MCC Bucket be placed in new Model 6 MCC section

Product Line:
Motor Control Centers

Environment:
Maintenance / Installation

Cause:
Clarification

Resolution:
The model 5 bucket will mount into a new Rev 05 ( Oct 2005 and Later) Mdl 6 MCC structure. You will need to use the shelf that comes in the new Model 6 MCC section and drill out the pin that is there for the butterfly to latch the Bucket in.
Note the old Model 5 shelf, or Pre Oct 2005  Mdl 6 MCC shelf,  will not work


 