Can I get a lug that would accommodate two 600 kcmil conductors on an MGP36800 breaker?

Issue:
MGP36800 breaker to accommodate (2) 600 kcmil conductor

Product Line:
Circuit Breakers

Environment:
Powerpact M Frame breaker

Resolution:
Use an AL800P6K lug kit for this application. It has a range of (2) #3/0 AWG-600 kcmil conductors, and contains 3 lugs per kit.