Are DC coils available for the 8903 type L contactors?

Issue:     
Are DC coils available for the 8903 type L contactors?  

Product Line:
8903 type L lighting contactors

Environment:
Products sold and used in the United States

Resolution:
Yes, they are. Use Form Y48 to substitute a DC coil for the AC coil. There is a 7 pole maximum (one pole is required to be used for switching the economizing resistor). A DC coil cannot be field modified from AC. For use on electrically held devices (open or enclosed) only.

Available Voltage
Voltages Code

24VDC V53  (Coil PN 31071-412-23)
This part number is the 24VDC coil used in the Class 8903 Type L electrically held lighting contactors.
Coil Details:
Coil resistance = 3 ohms
Economizing resistor used with this coil = 30 ohms
Inrush = 8A
Sealed = .727A

32VDC V54  (Coil PN 31071-412-26)
This part number is the 32VDC coil used in the Class 8903 Type L electrically held lighting contactors.
Coil Details:
Coil resistance = 4 ohms
Economizing resistor used with this coil = 50 ohms
Inrush = 8A
Sealed = .593A

48VDC V56  (Coil PN 31071-412-32)  
This part number is the 48VDC coil used in the Class 8903 Type L electrically held lighting contactors.
Coil Details:
Coil resistance = 8 ohms
Economizing resistor used with this coil = 125 ohms
Inrush = 6A
Sealed = .361A

115/125VDC V62  (Coil PN 31071-412-44)
This part number is the 115/125VDC coil used in the Class 8903 Type L electrically held lighting contactors.
Coil Details:
Coil resistance = 51 ohms
Economizing resistor used with this coil = 750 ohms
Inrush = 2.26A
Sealed = .144A

230/250VDC V66  (Coil PN 31071-412-53)
This part number is the 230/250VDC coil used in the Class 8903 Type L electrically held lighting contactors.
Coil Details:
Coil resistance = 213 ohms
Economizing resistor used with this coil = 3000 ohms
Inrush = 1.1A
Sealed = .072A

Ordering Example: 8903LO60V56Y48 or 8903LG40V62Y48