What is the AIC rating of a QOB3125SL subfeed lug kit?

Issue:
SFL kit AIC or available interrupting capacity rating

Product Line:
Panelboards

Environment:
NQ

Cause:
Installation

Resolution:
The subfeed lug kit would carry through the existing AIC rating of the panel it is attached to. The breakers in the panel determine the AIC rating, not the lugs or hardware.


 