What is the torque value needed for the 1/2"-13 VISI-TITE Nut used in EZM for connecting the horizontal cross buss together after the outer head has been broken off?

Issue:
Product Design Features

Product Line:
EZM Metering

Environment:
Main Horizontal bus connection nut

Cause:
Installation

Resolution:
50 lb.-ft. of torque is required for the inner hex head nut once the outer head of the VISI-TITE nut has been removed. This information is also provided on the wiring diagram of the EZM device.


 