What is the maximum number of contacts for MOC and TOC on metalclad breakers?

Issue:
What is the maximum number of  contacts for MOC and TOC on metalclad breakers?

Product Line:
Metalclad switchgear.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
MOC - Mechanism Operated Contacts. TOC - Breaker Truck Operated Contacts

Maximum Contacts MOC 7a 6b
Maximum Contacts TOC 6a 7b

MOC contacts are good in the Test and Connected Positions


 