On a 8536SBO2H30S how do you loop the wires on the overload with so little space between the contactor and overload?

Wiring solid state overload relays

Product Line:
NEMA Starters

Products sold and used in the United States

Wiring NEMA starter with solid state overload relay

You have to take the overload relay off the starter base plate in order to do this. There are also channels at the back of the overload to accept the looping turns.