What is the length of the S29343 telescoping shaft for the Powerpact H and J breaker?

Issue:
What dimension is needed for mounting the S29343 telescoping shaft?
 
Product Line:
Circuit Breakers
 
Environment:
Applies to Powerpact H and J circuit breakers
 
Resolution:
The dimension that is important is the distance from the back of the breaker to the front of the panel door. That dimension for the S29343 telescoping rotary handle is 9.8 inches minimum to 23.5 inches maximum. See instruction bulletin 48049-249-01
 