Technical FAQs

Ask a Question

Can a mechanically held Class 8903 Type LX lighting contactor be converted to electrically held?

Issue:     
Can a mechanically held Class 8903 Type LX lighting contactor be converted to electrically held?

Product Line:
8903 type LX lighting contactors 

Environment:
Products sold and used in the United States

Cause:
Can a mechanically held Class 8903 Type LX lighting contactor be converted to electrically held?

Resolution:
This conversion is not recommended and could create warranty and/or electrical inspector issues.

It may be possible to use the existing device by replicating the electrically held operation by interposing a relay with (1) normally open and (1) normally closed contact. See Form R6 wiring diagram for this application. Form R6 is a field installable option and would require a CA2SK11 relay of appropriate coil voltage and a 9999RLX bracket.


 
Was this helpful?
What can we do to improve the information ?