Can a Class T fuse be used in ANY of the 240Vac Max. General Duty Safety switches?

Issue:
Product design features

Product Line:
General Duty Safety Switches

Environment:
Class T Fuses

Cause:
Application or availability

Resolution:
NO. There are only a few General Duty Catalog numbers that will accept a class T fuse and those catalog numbers are D325NT, D325NTR, D326NT, D326NTR, T327N and T327NR.

ALL the remaining GDSS will ONLY accept the below fuses. SEE THE CURRENT DIGEST OR THE WIRING DIAGRAM ON EACH SWITCH FOR DETAILS.
The fuses are a Plug fuse, a Class H or K for 10k AIC MAX. and a Class J or R for 100k AIC Max. 