What is the difference between a trigger action mushroom head 22mm Emergency-stop push-pull or turn to release operator verses a standard non-trigger action operator?

Issue:
What is the difference between a trigger action mushroom head 22mm Emergency-stop push-pull or turn to release operator verses a standard non-trigger action operator?

Product Line:
Harmony Push Buttons

Environment:
Harmony 22mm

Cause:
Product Features

Resolution:
A standard operator can be depressed enough to open a normally closed contact without latching into the depressed position (teased). The trigger action units have a spring loaded mechanism that doesn`t depress the contact block until after it latches into the depressed position.


 