Can a Homeline load center and branch breakers be used in commercial applications?

Issue:
Product Design features

Product line:
Homeline load centers

Environment:
Location of use

Cause:
Application

Resolution:
The Homeline load centers are rated for single phase-3wire, 120/240Vac MAXIMUM, if the commercial application does NOT exceed the load center ratings, then they can be used in a commercial application. There is really no specific requirements for Residential vs commercial usage.
NOTE: For a commercial or industrial installation of Homeline load centers, the standard Conditions of Sale apply and the warranty period is only 18 months.