What is needed to mount a GV2ME to a LC1D 09 to D32?

Issue:
What adapter or combination block to be used together with the LAD31?

Product Line:
Tesys GV Manual Starter and Protectors
 
Environment:
US Product

Answer:
Either use a GV2AF3 combo block or a GV2AF4 block with LAD31 mounting plate . This later pair of parts will allow the front faces of the starter /protector and contactor to be aligned .