Is there an XB4 or XB5 push to test pilot light?

Issue:
Are push to test pilot lights available for 22mm?

Product Line:
Harmony Pushbuttons

Environment:
All Products

Resolution:
There is no push to test operator set up. Suggest using an illuminated pushbutton with (1) NO and (1) NC contact. The normal pilot light circuit is wired through the normally closed contact, and the test circuit is wired through the normally open contact. Customer will also have to jumper between the contacts.
 