What is the torque spec for the AL100FD (EDB breaker) lugs?

Issue:
Torque requirement for terminal lug on EDB, EGB, and EJB breakers
 
Product Line:
NF Panelboard Breakers
 
Environment:
EDB, EGB, EJB breakers 
 
Resolution:
For #14-#10 AWG AL/CU it is 35 lb-in. For #8-2/0 AWG AL/CU it is 50 lb-in.