On a SC816D200C, Series 002, what is the specified torque requirements for the incoming (line side) phase and neutral lugs?

Issue:
What is the specified torque requirements for the incoming (line side) phase and neutral lugs on a SC816D200C, Series 002?

Product Line:
Load Centers

Environment:
Combination Service Entrance Services

Resolution:
The line phase and neutral lugs wire binding screw should be torqued to 250 LB-IN. 